Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Types | Values |
Rated voltage Un | 240V/415V AC(1P),415V AC(2P,3P,4P) |
Rated current In | 80A,100A,125A |
Poles | 1P,2P,3P,4P |
Instant tripping type | C,D |
Rated short circuit breaking capacity(Icn) | 6000A |
Overcurrent protection properties | See Form 2,Diagram 1, 2 and 3 |
Mechanical and electrical life | See Form 3 |
Connection wire | See Form 4 |
Tightening torque | 2.5N.m |
Nominal temperatureºC | 30 |
Operated ambient temperatureºC | -5~+40 |
Stored ambient temperatureºC | -25~+70 |
Pollution level | 2 |
Protection level | IP20 |
Mounting type | 2 |
Overcurrent protection properties(Nominal temperature 30 ºC) | Form 2 | |||||
Item | Type | Test current | Initial status | Tripping or non tripping time limit | Expected result | Remarks |
a | 1.13In | Cold | t≤1h | Non tripping | ||
b | 1.45In | Test following the previous procedure; | t<1h | Trip | Current increases to stipulated value within 5s | |
Process after test | ||||||
BCD | ||||||
1s<t<60s | ||||||
c | 2.55In | Cold | (for In≤32A) | Trip | ||
1s<t<120s | ||||||
(for In>32A) | ||||||
B | 3In | |||||
d | C | 5In | Cold | t≤0.1s | Non trip | Connection of current by opening auxiliary switch |
D | 10In | |||||
B | 5In | |||||
e | C | 10In | Cold | t≤0.1s | Trip | Connection of current by opening auxiliary switch |
D | 20In | |||||